Technical data | IE2022 | IE2021 | IE2020 |
---|---|---|---|
Number of outputs | 8 | ||
Output connections | M12, screw type | M8, screw type | 8 mm, snap type |
Load type | ohmic, inductive, lamp load | ||
Nominal output voltage | 24 V DC (-15 %/+20 %) | ||
Max. output current | 2 A per channel, individually short-circuit proof, ∑ 4 A | ||
Short circuit current | max. 4 A | ||
Auxiliary power current | typ. 30 mA per channel | ||
Current consumption from US (without sensor current) | 25 mA | ||
Power supply connection | feed: 1 x M8 male socket, 4-pin; downstream connection: 1 x M8 female socket, 4-pin | ||
Bit width in the process image | 8 outputs | ||
Electrical isolation | channels/control voltage: no, between the channels: no, control voltage/fieldbus: yes, via IP-Link | ||
Operating/storage temperature | 0…+55 °C/-25…+85 °C | ||
Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 | ||
EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 | ||
Protect. class/installation pos. | IP 65/66/67 (conforms to EN 60529)/variable | ||
Approvals | CE, UL |